ZW20-12 Series High Voltage Vacuum Vacuum Circuit breaker

Takaitaccen Bayani:


Cikakken Bayani

Tags samfurin

ZW20-12 na waje HV Vacuum circuit breaker ne mai 3-lokaci AC 50Hz 12kV na waje canza kayan aiki

♦ Hanyar shigarwa: sandar igiya;

♦ Nau'in igiya: igiyoyin da aka haɗa;

♦ Aikace-aikacen: tashar tashar 12kV na waje, tashar wutar lantarki.

♦ Nau'in aiki: manual, lantarki, sarrafawa mai nisa.

 

Yanayin Muhalli

♦ Tsayi:

♦ Yanayin iska: -40°C~ + 40 ° C; canjin yanayin zafi na yau da kullun

♦ Gudun iska

♦ Matakan ƙazanta: IV;

♦ Wuraren shigarwa: Babu wuta, haɗarin fashewa, mummunar lalata sinadarai ko girgiza mai tsanani;

♦ Ƙarfin girgizar ƙasa:

 

Babban Ma'aunin Fasaha

A'A

Abu

Naúrar

Daraja

1 Ƙarfin wutar lantarki

kV

12

2 Jurewar wutar lantarki (minti 1) (bushe) tsaka-tsakin lokaci, ƙasa / karaya;

kV

42/48

(rigar) tsaka-tsakin lokaci, ƙasa

34

3 Ƙunƙarar walƙiya ta jure ƙarfin lantarki (interphase, ƙasa / karaya)

kV

75/85

4 Ƙididdigar halin yanzu A

630,1250

5 Ƙididdigar mita

Hz

50

6 An ƙididdige ɗan gajeren kewayawar halin yanzu

kA

20, 25

7 Ƙimar kololuwar jure halin yanzu (kolo)

kA

50, 63

8 rated ɗan gajeren lokaci jure halin yanzu

kA

20, 25

9 An ƙididdige ɗan gajeren da'ira yin halin yanzu

kA

50, 63

10 An ƙididdige ɗan gajeren lokacin da'ira S

4

11 An ƙididdige jerin aiki Lokaci

O-0.3S-CO-1 80S-CO

12 Ƙididdigar gajeriyar kewayawa mai karya lamba na yanzu Lokaci

30

13 Rayuwar injina Lokaci

10000

14 rated ƙarfin lantarki aiki (za a iya musamman) IN

220

15 Lokacin budewa

ms

≤80

16 Lokacin rufewa

ms

≤120

17 Cikakken lokacin karyewa

ms

≤100

18 An ƙididdige cajin kebul na karya halin yanzu

A

50

19 Daraja

E2~C2~M2(10000)

20 Ƙididdigar gajeriyar kewayawa mai karya lamba na yanzu Lokaci

30

Zane Gabaɗaya da Girman Shigarwa (naúrar: mm)

svv

Hanyoyin shigarwa

svv


  • Na baya:
  • Na gaba: