ZW32-24 na waje HV Vacuum circuit breaker shine 3-lokaci AC 50Hz 24kV na'urar sauya waje
♦ Hanyar shigarwa: sandar igiya;
♦ Tsarin aiki: kayan aiki na bazara da tsarin aiki na magnetic na dindindin;
♦ Nau'in igiya: igiyoyin da aka haɗa;
♦ Aikace-aikacen: tashar 24kV na waje, tashar wutar lantarki.
♦ Nau'in aiki, manual, lantarki, sarrafawa mai nisa.
Ka'idojin Samfur
♦ IEC62271-100 High Voltage Switchgear da Sarrafa Sashe na 100: AC-Cikin Wuta
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Bayanai na gama gari don Maɓallin Ƙarfin wutar lantarki da Kayan sarrafawa
Matsayi
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Ƙayyadaddun ƙayyadaddun ƙayyadaddun wutar lantarki na AC
Yanayin Muhalli
♦ Yanayin zafin jiki: -35°C~+ 40 ° C;
♦ Tsayi:
♦ Gudun iska
♦ Ƙarfin girgizar ƙasa:
♦ Matakan ƙazanta: IV;
♦ Wuraren shigarwa: Babu wuta, haɗarin fashewa ko ƙazanta mai tsanani.
Babban Ma'aunin Fasaha
A'a | Abu | Naúrar | Daraja |
1 | Ƙarfin wutar lantarki | kV | ashirin da hudu |
2 | Ƙididdigar halin yanzu | A | 630/1250 |
3 | Ƙididdigar mita | Hz | 50 |
4 | Ƙididdigar thermal current | kA | 20/25 |
5 | An ƙididdige ɗan gajeren kewayawar halin yanzu | kA | 20/25 |
6 | Ƙimar ƙarfin halin yanzu (kololuwa) | kA | 50/63 |
7 | An ƙididdige ɗan gajeren kewayawa na yanzu (kololuwa) | kA | 50/63 |
8 | Lokacin kwanciyar hankali na thermal | s | 4 |
9 | An ƙididdige jerin aiki | Lokaci | O-0.3S-CO-1 80S-CO |
10 | Mitar wutar lantarki na 1 min juriya irin ƙarfin lantarki (tsakanin lokaci, ƙasa / karaya) | kV | 65 |
Wutar walƙiya ta jure ƙarfin lantarki (kololuwa) (tsakanin lokaci, ƙasa/ karaya) | 125 | ||
Mitar wutar lantarki ta 1min ta biyu tana jure irin ƙarfin lantarki | 2 |
A'a | Abu | Naúrar | Daraja |
11 | Rayuwar injina | Lokaci | 10000 |
12 | An ƙididdige ɗan gajeren kewayawa lokacin karya na yanzu | Lokaci | 30 |
13 | An ƙididdige lokutan ɓarnar da'ira | Lokaci | 10000 |
14 | Nisan tuntuɓa | mm | 12± 1 |
15 | Fiye da tafiya | mm | 3 ± 1 |
16 | Nisa tsakanin lokaci-lokaci | mm | 380± 1.5 |
17 | Rufe lokaci uku da buɗe asynchronism | ms | ≤2 |
18 | Tsawon lokacin rufe lamba | ms | ≤2 |
19 | Lokacin rufewa | ms | 25-80 |
20 | Lokacin budewa | ms | 23-50 |
ashirin da daya | Matsakaicin saurin buɗewa | m/s | 1.1-1.7 |
ashirin da biyu | Matsakaicin saurin rufewa | m/s | 0.5-0.9 |
ashirin da uku | Main conductive kewaye juriya | mΩ | ≤80 |
Zane Gabaɗaya da Girman Shigarwa (naúrar: mm)
1. Tashar layin da ke fita na sama 2. Mai katsewa 3. Bututu mai rufewa 4. Ƙananan tashar layin da ke fita.
5. Shirye-shiryen gudanarwa 6. Haɗi mai sassauƙa 7. Insulating lever 8. Tushen matsi na lamba
9. Bude bazara 10. Turi 11. Injiniya mai fita shaft 12. Tsarin aiki
13. Mechanism Box 14. Transformer link board
1. Hannun aiki 2. Cire haɗin babban shaft 3. Hannun buɗewa / rufewa mai jujjuyawa
4. Hannun ajiyar makamashi 5. Alamar buɗewa / rufewa 6. Wiring plug 7. Transformer na yanzu
8. Insulator 9. Insulating frame 10. Insulating lever 11. Tashar layin da ke shigowa.
12. Cire haɗin ruwa 13. Tashar layin da ke fita 14. Mai watsewa
Hanyoyin shigarwa (Pole guda/giya guda biyu)