VS1-12 na cikin gida mai cire injin da'ira

Takaitaccen Bayani:


Cikakken Bayani

Tags samfurin

VS1-12 na cikin gida high-voltage vacuum circuit breaker ne na cikin gida switchgear for uku-lokaci AC 50Hz rated ƙarfin lantarki na 12kV ikon tsarin, a matsayin kariya da kuma kula da naúrar ga ikon kayan aikin grid da masana'antu da kuma ma'adinai Enterprises. Ya dace da aiki akai-akai a ƙarƙashin ƙimar aiki na halin yanzu, ko don wurin da gajeriyar kewayawa ta karye ta hanyoyi da yawa.
Mai watsewar kewayawa yana ɗaukar ƙirar tsarin aiki da jikin mai watsewar kewayawa, wanda za'a iya amfani da shi azaman kafaffen naúrar shigarwa ko naúrar cirewa.

VS1-12 na cikin gida HV injin da'ira mai watsewa shine na'ura mai sauyawa na cikin gida AC 50Hz 12kV mai lamba 3.

♦ Hanyar shigarwa: nau'in cirewa, nau'i mai mahimmanci, nau'in da aka ɗora gefe;

♦ Tsarin aiki: na'ura mai ƙididdigewa na bazara, tsarin aiki na magnetic na dindindin;

♦ Nau'in sanda: sandar da aka haɗa, sandar da aka saka;

♦ Aikace-aikacen: switchgear KYN28-12, XGN-12.

♦ Na biyu filogi: 58 fil, 64 fil.

Ka'idojin Samfur

♦ IEC62271-100 High Voltage Switchgear da Sarrafa Sashe na 100: AC-Cikin Wuta

♦ GB1984 High Voltage AC Circuit-breakers

♦ GB/T11022 Ƙididdiga gama-gari don Maɗaukakin Maɓalli na Wutar Lantarki da Matsayin Sarrafa

♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers

♦ DL/T402 Ƙayyadaddun ƙayyadaddun ƙayyadaddun wutar lantarki na AC

 

Yanayin Muhalli

♦ Yanayin zafin jiki: -15 ° C ~ + 40 ° C;

♦ Tsayi:

♦ Dangi zafi: matsakaita kullum

♦ Ƙarfin girgizar ƙasa:

♦ Wurare ba tare da wuta ba, haɗarin fashewa, mummunan ƙazanta, lalata sinadarai, da kuma girgiza mai tsanani.

 

Babban Ma'aunin Fasaha

A'a

Abu

Naúrar

Daraja

1 Ƙarfin wutar lantarki kV

12

2 Mitar wutar lantarki na 1 min jure irin ƙarfin lantarki

42

3 Ƙimar walƙiya mai ƙima ta jure ƙarfin lantarki

75

4 Ƙididdigar mita Hz

50

5 Ƙididdigar halin yanzu A

630, 1250, 1600, 2000, 2500,

3150, 4000

6 An ƙididdige ɗan gajeren kewayawar halin yanzu kA

20, 25, 31.5, 40

7 Ƙididdigar ɗan gajeren lokaci jure halin yanzu

20, 25, 31.5, 40

8 An ƙididdige ɗan gajeren lokacin da'ira s

4

9 Ƙimar kololuwa ta jure halin yanzu

kA

50, 63, 80, 100

10 An ƙididdige ɗan gajeren da'ira yin halin yanzu

50, 63, 80, 100

11 Mitar wutar da'ira ta biyu tana jure irin ƙarfin lantarki (minti 1) IN

2000

12 rated guda / baya-baya capacitor banki karya halin yanzu A

630/400 (800/400 don 40kA da

50 kA)

 

A'a

Abu

Naúrar

Daraja

13

rated capacitor banki rufe inrush halin yanzu A

12.5

14

Lokacin buɗewa (ƙimar ƙarfin lantarki)

ms

20-50

15

Lokacin rufewa (ƙimar ƙarfin lantarki)

ms

35-70

16

Rayuwar injina

Lokaci

10000

17

An ƙididdige lambar karya na yanzu

Lokaci

10000

18

An ƙididdige lambar ɓarnar gajeriyar kewayawa na yanzu

Lokaci

50 (30 don 40kA;20 da 50kA)

19

Motsawa da kafaffen lambobi Tarin kauri da aka yarda da lalacewa mm

3

20 Ƙididdigar ƙarfin ƙarfin aiki na rufewa IN

AC/DC110/220

ashirin da daya Ƙididdigar wutar lantarki mai aiki
ashirin da biyu Ƙididdigar ƙarfin lantarki na injin ajiyar makamashi

IN

70 (80 ror 40kA da 50kA)

ashirin da uku Ƙarfin ƙima na injin ajiyar makamashi
ashirin da hudu Lokacin ajiyar makamashi s

25 Share tsakanin buɗaɗɗen lambobi mm

11 ± 1

26 Fiye da tafiya mm

3.5 ± 0.5

27 Tuntuɓi lokacin rufe billa ms

≤2 (≤3 don 40kA da 50kA)

28 Budewa da rufe asynchronism kashi uku ms

≤2

29 Matsakaicin saurin buɗewa

m/s

0.9-1.2

30 Matsakaicin saurin rufewa

m/s

0.5-0.8

31 Main conductive kewaye juriya

≤60 (630A) ≤50(1250A) ≤35(1600-2000A) ≤25(sama da 2500A)

32 Rufe matsin lamba na lambobin sadarwa N

2000± 200 (20kA)

2400± 200(25kA)

3100± 200 (31.5kA)

4250± 250 (40kA)

6500± 500 (50kA)

33 An ƙididdige jerin aiki

O-0.3s-CO-180s-CO

O-180s-CO-180s-CO (50kA)

 

 


  • Na baya:
  • Na gaba: